Monoblock

GHO-TRON

GHO-TRON 6.8500 R

  • Operation: two stage progressive/modulating mechanical;
  • Emission class: Low NOx class 2 (<120 mg/kWh) according to EN676 in gas

WORKING DIAGRAM

TECHNICAL DATA

Minimum power output (kW) 2000
Maximum power output (kW) 8500
Minimum gas pressure (mbar) 85
Maximum gas pressure (mbar) 700
Fan motor (kW) 18.5
Protection level IP42

OTHER AVAILABLE CONFIGURATIONS

  • Continuous ventilation;
  • High temperature;
  • High viscosity suitable for 118 cSt (15°E) at 80°C

OVERALL DIMENSIONS

Dimensions-GHO-6.jpg
A B C D E F G G1 H1 I L M N O
1370 740 630 470 1640 420 775 850 1270 460 460 M20 195 232

Reserved area