Monoblock

GHO-TRON

GHO-TRON 4.3000 R

  • Operation: two stage progressive/modulating mechanical;
  • Emission class: Low NOx class 2 (<120 mg/kWh) according to EN676 in gas

WORKING DIAGRAM

TECHNICAL DATA

Minimum power output (kW) 650
Maximum power output (kW) 3000
Minimum gas pressure (mbar) 22
Maximum gas pressure (mbar) 700
Fan motor (kW) 7.5
Protection level IP42

OTHER AVAILABLE CONFIGURATIONS

  • Continuous ventilation;
  • High temperature;
  • High viscosity suitable for 118 cSt (15°E) at 80°C

OVERALL DIMENSIONS

Dimensions-GHO-4.jpg
A B C D D1 E F G G1 H1 I L M N O
1288 610 678 330 530 1130 290 471 750 280 315 315 M16 195 250

Reserved area